Addressable Monitor Modules: Features
The Monitor Module is an input device designed to interface with third-party equipment, such as security contacts, water flow switches, and pull stations, with a Fire Alarm Control Panel (FACP).
It features a red blinking LED to indicate normal operation and a steady-state LED for activated conditions.
The module includes DIP switches for address configuration, and its monitoring circuit is supervised for fault conditions.
Addressable Monitor modules are used to supervise a circuit of dry-contact input devices.
- Input Single normally open potential free contact
- Wall mount facility
- Digital addressable communications
- DIP switch for addressing of modules
- Pure ABS material
Electrical Specification
Operating Voltage |
24 VDC Nominal. |
Alarm Current |
2.7 mA Max.(Latched) |
Standby Current |
0.7 mA |
End of Line Resistor | 47K Ohms |
Loop Impedance | 40 Ohms |
IDC wiring Resistance | 100 Ohms Max |
IDC Voltage |
8 V Max |
Operating Temperature | 0°C to 49°C / 32°F to 120°F
|
Storage Temperature | 0°C to 60°C |
Humidity | 93 ± 2% RH (non-condensing) at 32 ±2° C / 90 ±3° F |
Technical Specification
Dimensions | (95 W X 75 H X 24D) mm |
Colour | Black |
Material | FR ABS plastic |
Weight | 350 g |